Why operators were too hot in a 19 °C room
- HVAC systems
- Cleanroom infrastructure
- EN 16798-1
- Thermal stress


The challenge
Operators in a production plant kept reporting that their compartments were too hot, even though the rooms were running at their design conditions.
What we did
We reviewed the as-built documentation, analysed trend data from winter and summer, calculated how much sensible heat the ventilation removes from each room, and ran a comfort simulation to EN 16798-1.
What we found
The rooms were not too warm, at 19 to 21 °C. The operators were. A vapour-tight protective suit combined with heavy work puts them outside the comfort range, even at 19 °C and 50 % RH.
Predicted share of dissatisfied operators (PPD)
18 %at 19 °C
up to 28 %at 21 °C, still within specification
The result
Within the limits of the existing installation, we proposed how to lower the temperature in the production area so operators can work more comfortably. We started with measures of limited impact, such as adjusted supply setpoints, and added physical adaptations to reach the best possible result.