All projects
Humidity control for a 50,000 m³ high-bay warehouse
- HVAC systems
- Black utilities & energy
- 50,000 m³
- 15–25 °C
- 3 × 20,000 m³/h
- 2+1 redundancy

The challenge
A temperature-controlled high-bay warehouse struggles to stay within its 15 to 25 °C specification. The client also wants the installation to hold relative humidity between 35 and 65 %, but the existing system has no way to add or remove moisture.
What we did
We reviewed the existing installation and analysed a full year of its trend data. Then we let the psychrometrics settle the question. Outdoor air warmed to 20 °C in winter ends up at 10 to 34 % RH. Cooled to 20 °C in summer, it sits at 79 to 90 %. Neither lands in the band, so it can only be held with active humidification and dehumidification.
Outdoor air brought to 20 °C, against the required band
35–65 % required
Winter air
10–34 %
10–34 %
Summer air
79–90 %
79–90 %
0 % RH100 % RH
We compared three concepts and worked the preferred one out to a cost estimate.
The result
- The existing air handling units renewed as three units of 20,000 m³/h in a redundant 2+1 configuration. The warehouse stores critical products, so it stays in specification with one unit out of service.
- The existing jet-duct network re-used.
- Permanent mapping sensors in the racks, so temperature and humidity are followed across the whole volume, not at a single point.
- A phased approach, worked out around the client's operations so the warehouse keeps running during the works.